banner
Products
Proven and reputable supplier of outstanding services
Onccy Type 1 2, T1 T1, B C, I II, Iimp 10ka, Lmax 100ka Quick Wiring SPD Surge Protector

Onccy Type 1 2, T1 T1, B C, I II, Iimp 10ka, Lmax 100ka Quick Wiring SPD Surge Protector

A leading provider of AC Surge Protection Device An AC Surge Protection Device (SPD) is a vital component used in electr;
Basic Info
Model NO. EAP
Shape Cuboid
Material Ceramic
Certification ROHS, CE, TUV
Brand Onccy
Nominal Discharge Current 20ka
Lmax 40ka
Pole 2p/3p
I Ec/En/UL Category Type2
Degree of Protection IP20
Transport Package by Sea/Air
Specification Export Cartons
Trademark Onccy
Origin China
HS Code 8536490090
Production Capacity 1000000PC/Year
Product Description

A leading provider of AC Surge Protection Device

An AC Surge Protection Device (SPD) is a vital component used in electrical systems to safeguard sensitive equipment and appliances from voltage surges, also known as transient overvoltages. Voltage surges are sudden increases in voltage that can occur due to various reasons, such as lightning strikes, switching of large electrical loads, or power grid disturbances. These surges can damage or degrade electronic devices, causing malfunctions, reduced lifespan, or complete failure.

AC Surge Protection Device (AC SPD) T1+T1, B+C, Class I+II

Product Benefits

  • Prewired Modular Complete Unit, Consisting of A Base Part and Plug-in Protection Modules.
  • Plug-in Protection Module, Easily Installation and Maintainance.
  • High Energy Varistor, Response Time Less Than 25 Nanosecond.
  • Optional Remote Signalling Contact(FM) for Monitoring Device (Floating Changeover Contact)
EAP Series Surge Protection Device was designed and manufactured, complying standard GB/T18802.1 IEC/EN 61643-11 , Rated voltage 275V~,320V~,385V~,440V~,Maximum discharge current 50kA,High Energy Varistor, high effective for lightning protection.AC Surge Protection Device SPD Type 1 2, T1 T1, B C, I II, Iimp 10kA,lmax 100kA is designed to be the best possible solution for protecting service entrances at industrial sites, particularly those with existing lightning protection systems or mesh cage applications. This sort of surge protection can protect all electrical installations from lightning strikes by discharging the current generated by a lightning surge and preventing its spread to the equipment. The current waveform of the Type 1 2/Class B C, I II SPD is 10/350 μs.

Product Benefits

  • Prewired Modular Complete Unit, Consisting of A Base Part and Plug-in Protection Modules.
  • Plug-in Protection Module, Easily Installation and Maintainance.
  • High Energy Varistor, Response Time Less Than 25 Nanosecond.
  • Optional Remote Signalling Contact(FM) for Monitoring Device (Floating Changeover Contact).

Technical Data

IEC Electrical
Nominal AC Voltage (50/60Hz)Uo /Un230V 230V 230V 400V
Maximum Continuous Operating Voltage (AC)Uc275V 320V 385V 440V
Nominal Discharge Current (8/20 μs)In20kA 20kA 20kA 20kA
Maximum Discharge Current (8/20 μs)Imax50kA 50kA 50kA 50kA
Impulse Discharge Current (10/350 μs)I Imp12.5kA 12.5kA 10kA 10kA
Specific EnergyW/R39kJ/Ω 39kJ/Ω 25kJ/Ω 25kJ/Ω
ChargeQ6.25As 6.25As 5As 5As
Voltage Protection LevelUp1500V 1500V 1800V 2000V
Response TimetA<25ns
Back-Up Fuse (max)160A gL
Short-Circuit Current Rating (AC)I SCCR25kA / 50kA
TOV Withstand 5sUT335V 335V 335V 580V
UT440V 440V 440V 765V
TOV 120minModeSafe Fail Safe Fail Safe Fail Safe Fail
Number of Ports1
UL Electrical
Maximum Continuous Operating Voltage (AC)MCOV275V 320V 385V 440V
Voltage Protection RatingVPR900V 1200V 1350V 1500V
Nominal Discharge Current (8/20 μs)In20kA 20kA 20kA 20kA
Short-Circuit Current Rating (AC)SCCR150kA 150kA 150kA 200kA
Mechanical & Environmental
Operating Temperature RangeTa-40oF to +158oF [-40oC to +70oC]
Permissible Operating HumidityRH5%…95%
Atmospheric pressure and altitude80k Pa … 106k Pa / -500m … 2000m
Terminal Screw TorqueMmax39.9 Ibf·in [2.0~2.5 N.m]
Conductor Cross Section (max)2 AWG (Solid, Stranded) / 4 AWG (Flexible)
35mm2 (Solid, Stranded) / 25mm2 (Flexible)
Mounting35mm DIN Rail, EN 60715
Degree of ProtectionIP20(built-in)
Housing MaterialThermoplastic: Extinguishing Degree UL 94 V-0
Thermal ProtectionYes
Operating State / Fault IndicationGreen: ok / Red: defect
Remote Contacts (RC)Optional
RC Switching CapacityAC:250V / 0.5A; DC:250V / 0.1A; 125V / 0.2A; 75V / 0.5A
RC Conductor Cross Section (max)16AWG (Solid) / 1.5mm2 (Solid)

Product model
IEC Electrical
Nominal AC Voltage (50/60Hz)Uo /Un230V
Maximum Continuous Operating Voltage (AC) (L-N) / (N-PE)Uc275V/255V320V/255V385V/255V440V/440V
Nominal Discharge Current (8/20 μs) (L-N) / (N-PE)In20kA/20kA20kA/20kA20kA/20kA20kA/20kA
Maximum Discharge Current (8/20 μs) (L-N) / (N-PE)Imax50kA/50kA50kA/50kA50kA/50kA50kA/50kA
(L-N) / (N-PE)I Imp12.5kA / 25kA / 50kA
Voltage Protection Level (L-N) / (N-PE)Up<1500V / 1500V<1500V / 1500V<1800V / 1500V<2000V / 1500V
Response Time (L-N) / (N-PE)tA<25ns / 100ns
Back-Up Fuse (max)160A gL
Short-Circuit Current Rating (AC) (L-N)I SCCR25kA / 50kA
TOV Withstand 5s (L-N)UT335V
(L-N)UT440V
TOV 120min (L-N)ModeSafe Fail
Number of Ports1
UL Electrical
Maximum Continuous Operating Voltage (AC)MCOV275V320V385V440V
Voltage Protection RatingVPR900V1000V1200V1200V
Nominal Discharge Current (8/20 μs)In20kA20kA20kA20kA
Short-Circuit Current Rating (AC)I SCCR150kA150kA150kA200kA
Mechanical & Environmental
Operating Temperature RangeTa-40oF to +158oF [-40oC to +70oC]
Permissible Operating HumidityRH5%…95%
Atmospheric pressure and altitude80k Pa … 106k Pa / -500m … 2000m
Terminal Screw TorqueMmax39.9 Ibf·in [2.0~2.5 N.m]
Conductor Cross Section (max)2 AWG (Solid, Stranded) / 4 AWG (Flexible)
35mm2 (Solid, Stranded) / 25mm2 (Flexible)
Mounting35mm DIN Rail, EN 60715
Degree of ProtectionIP20(built-in)
Housing MaterialThermoplastic: Extinguishing Degree UL 94 V-0
Thermal ProtectionYes
Operating State / Fault IndicationGreen: ok / Red: failure
Remote Contacts (RC)Optional
RC Switching CapacityAC:250V / 0.5A; DC:250V / 0.1A; 125V / 0.2A; 75V / 0.5A
RC Conductor Cross Section (max)16AWG (Solid) / 1.5mm2 (Solid)

Product model
IEC Electrical
Nominal AC Voltage (50/60Hz)Uo /Un230V
Maximum Continuous Operating Voltage (AC) (L-N) / (N-PE)Uc275V/255V320V/255V385V/255V440V/440V
Nominal Discharge Current (8/20 μs) (L-N) / (N-PE)In20kA/20kA20kA/20kA20kA/20kA20kA/20kA
Maximum Discharge Current (8/20 μs) (L-N) / (N-PE)Imax50kA/50kA50kA/50kA50kA/50kA50kA/50kA
(L-N) / (N-PE)I Imp12.5kA / 25kA / 50kA
Voltage Protection Level (L-N) / (N-PE)Up<1500V / 1500V<1500V / 1500V<1800V / 1500V<2000V / 1500V
Response Time (L-N) / (N-PE)tA<25ns / 100ns
Back-Up Fuse (max)160A gL
Short-Circuit Current Rating (AC) (L-N)I SCCR25kA / 50kA
TOV Withstand 5s (L-N)UT335V
(L-N)UT440V
TOV 120min (L-N)ModeSafe Fail
Number of Ports1
UL Electrical
Maximum Continuous Operating Voltage (AC)MCOV275V320V385V440V
Voltage Protection RatingVPR900V1000V1200V1200V
Nominal Discharge Current (8/20 μs)In20kA20kA20kA20kA
Short-Circuit Current Rating (AC)I SCCR150kA150kA150kA200kA
Mechanical & Environmental
Operating Temperature RangeTa-40oF to +158oF [-40oC to +70oC]
Permissible Operating HumidityRH5%…95%
Atmospheric pressure and altitude80k Pa … 106k Pa / -500m … 2000m
Terminal Screw TorqueMmax39.9 Ibf·in [2.0~2.5 N.m]
Conductor Cross Section (max)2 AWG (Solid, Stranded) / 4 AWG (Flexible)
35mm2 (Solid, Stranded) / 25mm2 (Flexible)
Mounting35mm DIN Rail, EN 60715
Degree of ProtectionIP20(built-in)
Housing MaterialThermoplastic: Extinguishing Degree UL 94 V-0
Thermal ProtectionYes
Operating State / Fault IndicationGreen: ok / Red: failure
Remote Contacts (RC)Optional
RC Switching CapacityAC:250V / 0.5A; DC:250V / 0.1A; 125V / 0.2A; 75V / 0.5A
RC Conductor Cross Section (max)16AWG (Solid) / 1.5mm2 (Solid)

Onccy Type 1 2, T1 T1, B C, I II, Iimp 10ka, Lmax 100ka Quick Wiring SPD Surge Protector

Onccy Type 1 2, T1 T1, B C, I II, Iimp 10ka, Lmax 100ka Quick Wiring SPD Surge Protector

Onccy Type 1 2, T1 T1, B C, I II, Iimp 10ka, Lmax 100ka Quick Wiring SPD Surge Protector

Onccy Type 1 2, T1 T1, B C, I II, Iimp 10ka, Lmax 100ka Quick Wiring SPD Surge Protector

Onccy Type 1 2, T1 T1, B C, I II, Iimp 10ka, Lmax 100ka Quick Wiring SPD Surge Protector


FAQ
Q: Are you trading company or manufacturer ?
A: We are manufacturer. We have 30,000 square meters of self-owned plant
Q: Do you have any certificates?
A: Yes,we have UL, TUV, CB, SAA, CCC, CE and other certifications
Q: How do we make a quick response to customer , 5 inquiry ?
A: Our professional team will reply you online or by email,Skype, whatsApp and so on
Q: Do you have any exporting experience?Which countries did you export to before?
A: We have lots of exporting experience and customers in many countries,such as America, Japan,Australia,UAE,Canada,Vietnam,Turkey,Thailand,Russia,UK,etc
Q:Can you supply samples for checking ?
A: Yes, we can supply samples, pls contact for detailed required
Q:How long is your delivery time?
A: Generally it is within 3days for small qty. Or it is around 15-20 days to a general order
Q: What is the standard of package of your goods?
A: Export standard package or special package according to customer requirement
Q:How about inspection?
A: We have the whole inspection system from raw material to end products include transient test, delay test,mechanical life test and so on
Q:What is the service offered by company?
A: We have the professional engineer team which can design and develop the mould to arrive different customer requirements. We also have the professional sales team to offer good service from pre-sale to after-sale.

Send inquiry